Servo Stabilizer
(Oil-cooled) |
| |
|
CAPACITIES :
|
1)
0.5 KVA to 60 KVA I
PH |
| |
2)
1.5
KVA to 2000 KVA 3 PH |
| |
|
|
SPECIFICATIONS : |
|
Input Voltage Range
|
300 V 460 V AC 50 Hz 3 PH |
|
Other Input Ranges |
245 V- 460 V AC 3Ph
|
|
340 V- 460 V AC 3Ph
|
|
360 V- 460 V AC 3Ph
|
|
other ranges as per customer
requirement |
|
Output Voltage |
380 V / 400 V/ 415 V AC 3Ph 50
Hz
|
|
System |
Unbalanced 4 Wire : R Y B N
|
|
Connections
|
Star |
|
 |
|
| |
|
Operating Frequency |
47Hz to 53 Hz |
|
Output Voltage Adjustable |
380 V to 415 V AC in 3Ph |
|
220 V to 240 V AC in 1Ph |
|
Output Voltage Regulation |
ą 1% |
|
Over Load Capacity |
120% |
|
Correction Rate |
15 V / 20 V / 35 V / Sec-1Ph |
|
25 V / 35 V / 60 V / Sec-3Ph |
|
110V/Sec for D.C.
Motor controlled |
|
Waveform Distortion |
Nil |
|
Output Waveform |
True Reproduction of Input |
|
Insulation
|
Class 'B'
|
|
Short CKT Period & percentage |
300 % for 250 m.sec.
|
|
Normal Operating Temperature
|
0ēC to 45ēC |
|
Climatic Conditions
|
90 % RH.Max.Non-Condensing at
35ē C
|
|
Mode of System
|
Fully Automatic / Manual
|
|
System
Construction |
AS PER IS : 9815 of 1994 |
|
| |
|
STANDARD
PROTECTIONS |
-
Low voltage protection
-
High Voltage protection
-
Overload Protected with MCB /
MCCB
-
Single Phasing Preventer
|
|
PANEL
INDICATIONS |
|
|
|
Input |
ON |
|
Output
|
ON |
|
Input |
Low |
|
Input |
High |
|
Output |
Cut-off
|
|
|
|
|
PANEL METERS |
-
Volt Meter With Selector Switch
to read Input/Output Voltages, phase to phase and phase to neutral.
-
Ammeter With Selector Switch (From 15 KVA 3Ph onwards )
|
|
OPTIONAL
ACCESSORIES IN 3 Ph SYSTEM |
- INPUT UNDER
/ OVER VOLTAGE TRIP
- OUTPUT UNDER
/ OVER VOLTAGE ALARAM
- DIGITAL VOLTMETER / AMMETER
- FREQUENCY METER (Digital / Analog)
- FREQUENCY TRIP HIGH / LOW
ADJUSTABLE (With setting thumb Wheel switch)
- MCB/MCCB FOR OUTPUT
- Dimmer
Protection Arrangement
- Phase
Reversal Protection
|
|
SAILENT
FEATURES |
|
|
|
Quick
Response |
Quickest
response time 10 ms. (half a cycle) |
|
High
Overload capacity |
Higher
overload capabilities for high starting and regenerative
currents repeated frequency in CNC Machines. |
|
Fast
Correction |
Fastest rate
of correction up to 70 V/sec. |
No Hunting,
No Oscillations, No Noise Generation |
Machine
Wound Variable Auto Transformer, with special Carbon Brush to
minimize carbon deposit and for smooth
commutation. |
|
|
|
|
ENERGY SAVINGS |
-
Better
efficiency of 98% achieved by use of prime grade Lamination.
-
Electrolytic
copper wires of 99.99% purity.
-
Specially
designed transformers to minimize losses.
-
ALSO, Special
sensing circuit to ensure constant Output Voltage even with distorted
input from D.G. set. Conforms to stringent Defence specifications.
Tropicalised design
|
|
|
|
|
|